It can be processed according to the drawings and samples, receive oem orders, accept wholesale and customization. Provide a complete set of motor protection system solutions. Apply Motor power:5000~10000KW,Diameter Size(mm):10600×2480×1500 or Customized
RZHV series high voltage inverter is the third generation of high voltage frequency conversion speed regulating device which is independently developed, designed and produced by Rongzhi Electric. The system adopts the current stable, reliable and advanced power unit cascade technology, with DSP+FPGA+CPL D processor as the control core, PLC as the user interface, and touch screen as the human-computer interaction interface. Inject the most advanced motor vector control algorithm has high control precision, fast response speed, low frequency torque and other characteristics has been widely used in the fan. hoist and other loads of energy-saving speed regulation and process improvement, solve the problem of using, for users to create profit.
Operating Environment
In order to ensure that the speed regulating device can run stably and reliably for a long time, the installation and working environment of frequency conversion speed regulating device should meet the following requirements.
The inverter room should be equipped with sufficient air conditioning equipment, dehumidification equipment, dust sealing equipment, to ensure that the operating environment temperature of equipment meets the requirements of 6.2 Operating environment in DL-T994-2006.
Touch screen
Power Cabinet
Control cabinet
Optical fiber communication with strong anti-interference ability is used between the main control board and the unit.
Technical Parameters
MVD Item
AMV-IV~250~1500
AMV-IV~500~9800
AMV-IV~800~12500
Capacity of MVD(kVA)
250~1500
500~9800
800~12500
Apply motor Power(kW)
200~1250
400~7800
630~10000
Rated input Current(A)
50~300
50~960
50~780
Rated input Voltage(V)
3000±10%
6000±10%
10000±10%
Rated input frequency(Hz)
45~55
Input power factor
0.96(>20% Load)
Effiency
Under Rated load>0.95
Range of output frequency(Hz)
5~60(Other frequency should be stated before booking)
Output frequency resolution (Hz)
0.01
Overloading
120% anti-time limit of 1 minute, 150% immediate protection
Analog input
2 lines(0~10)V/(4~20)mA
Analog Output
4 lines(0~10)V/(4~20)mA
Acceleration time(s)
0.1~3000
Input/Ouput Switch Qty
Standard Setting: Input 6,output 6 lines; Can be options
Inner earthing Resistance(Ω)
<0.1
Ambient(°C)
0~40 (°C)
Storage / transport temperature(°C)
-40~70(°C)
Cooling
Air Cooling
Running Decibel(dB)
≤85
Ambient humidity
<90%,No Congeal
Install Altitude(m)
≤1000M,If more than 1000meter,need to booked.
IP Class
IP4X
Diameter Size(mm)
4800×2450×1300
200~630KW
6500×2450×1300
400~3250KW
7800×2450×1300
630~5000KW
5600×2450×1300
630~1250KW
7800×2450×1300
3250~7800KW
10600×2480×1500
5000~10000KW
Net Weight(kg)
3000~5000
200~630KW
6000~8000
400~3250KW
8000~14000
6300~5000KW
3500~6000
630~1250KW
10000~16000
3250~7800KW
15000~23000
5000~10000KW
Item |
Two Limit |
Four limit |
||||
Input |
Voltage Classes |
AC3PH |
AC3PH |
|||
3KV | 6KV | 10KV | 6KV | 10KV | ||
Voltage Fluctuation Range |
-20%-+10% |
|||||
Voltage Frenquency |
50/60Hz;±5% |
|||||
Power Factor |
≥ 0.97(full load) |
|||||
System Efficiency |
≥ 0.96(full load) |
|||||
Current Harmonics |
≤ 4% |
≤ 2% |
≤ 4% |
|||
Output |
Voltage Range |
0- Rated Voltage |
||||
Frequency Range |
0-120Hz; can be customized |
|||||
Current Harmonics |
≤ 4% |
≤ 2% |
||||
Control Performance |
Control Mode |
High performance VF control,open-loop vector,close-loop vector control |
||||
Speed Ratio |
1:50(VF);1:100(SVC);1:200(VC) |
|||||
Velocity Control Accuracy |
±1%(VF); ±0.4%(SVC); ±0.2%(VC) |
|||||
Torque Response Time |
< 200ms(SVC);< 100ms(VC) |
|||||
Pull-in Torque |
0.5Hz150% rated torque(SVC);0Hz180% rated torque(VC) |
|||||
Overload Protection |
120%:120s;150%:5s;200%: protection |
150%:60S;200%: protection |
||||
Add-subtract Speed Time |
0-6000S, can be customized |
|||||
Signal Distribution Unit |
On-off Input |
18 channels digital input (expandable, programmable) |
||||
On-off Output |
12 channels digital output (expandable, programmable) |
|||||
Analog Input |
Four analog inputs (0-10V or 0-20mA)) |
|||||
Analog Output |
2 channels analog input (0-10V or 0-20mA) |
|||||
Protection |
System protection |
Overcurrent, overvoltage, undervoltage, overload, phase loss, imbalance, overheat, overtemperature, access control, communication, etc |
||||
Cell protection |
Undervoltage, overvoltage, overtemperature, phase loss, optical fiber, overcurrent, etc |
|||||
Human-computer interface |
10 inch touch screen |
|||||
Communication way |
Support Modbus agreement,profibus, Profinet optional |
|||||
Installation Method |
Cabinet assembly |
|||||
Protection grade |
IP30 |
|||||
Noise Level |
≤ 75dB |
|||||
Incoming / outgoing lines |
Into the out |
|||||
Cooling Type |
Forced air cooling |
|||||
control source |
AC380V,three-phase four-wire |
|||||
Mean time to failure |
50000h |
|||||
Operating ambient temperature |
-20℃ -+40℃ |
|||||
Altitude |
1000m below,1000m ,each 100m Derating 1% |
|||||
Storage temperature |
Stored in free from dust, direct sunlight, combustible or corrosive gas, oil, water vapor and vibration |
|||||
Vibration amplitude |
0.59g below |
Product Feature
1.Three control techniques
● High performance VF control: motor universal control mode, support a variety of control curves and VF separation function
● Open loop vector :high precision control mode, no need to install speed sensor
● Closed-loop vector :ultra high precision control mode, can support additional encoder
2.Four quadrant drive technology
The power unit uses IGBT for rectification to realize bi-directional flow of capacity, energy saving and environmental protection. Full power feedback capability.
3.LVRT low voltage crossing technology
Wide range voltage immunity.
The system has AVR (automatic voltage regulation)
function to meet the harsh power grid environment:
85%-85% derating output
85%-110% full load output
110%-120% derating output
4.Excellent low frequency control technology
Advanced dead zone compensation technology, good low frequency waveform; The optimized low frequency oscillation suppression algorithm will not cause motor resonance.
5.Unit bypass technique
Same bypass. When a unit fails, the system automatically bypasses each corresponding unit, which is suitable for derating operations Neutral offset bypass. High voltage output capacity, strong field adaptability.
6.Full frequency speed tracking
The system can accurately track the current speed and direction of the motor without the need to install speed sensors. The system can start automatically when the power failure is recovered within the specified time.
7.Master control technology
●The host and slave are connected by CAN bus to balance the power of multiple devices.
● Wide input voltage range, more suitable for domestic power grid conditions.
● No special requirements for motor, suitable for ordinary high voltage motor, no length limit for motor cable.
● Equipped with a comprehensive operation monitoring system, with up to tens of thousands of operation log monitoring, can timely and accurately lock the fault point.
● Friendly all-Chinese interface and perfect self-diagnosis function.